Enclosure cooling unit “COOL CABI”
OCA-600BC-200V(-CE)
Lateral mounting type (Standard)
Features
- Temperature indication
- High temperature alarm output
- Ease of maintenance
- Mountable either on the outer wall or being recessed as the space demands
- For other details, please go to “Product outline”.
Specifications
Model |
OCA-600BC-200V |
OCA-600BC-200V-CE |
Type of mounting |
Lateral mounting |
Cooling capacity ※1 |
500/610W |
Rated voltage |
Single phase 200VAC±10% |
Current consumption ※2 |
Rated |
2.5/2.3A or less |
Max. |
2.7/2.6A |
Starting current |
8.7/8.3A |
Power consumption ※2 |
Rated |
480/450W |
Max. |
540/530W |
Refrigerant |
R407C (260g) |
Working temperature ※3 |
+20 to +50℃ |
Temperature setting range ※3 |
+30 to +45℃ (Initial setting:+35℃) |
External output |
Alarm output (no voltage c contact: 250VAC/30VDC 3A resistance load) |
Display |
Internal temperature, Alarm code/Operation lamp, Alarm lamp |
Function |
Off-temperature alarm, Detection of abnormal heat dissipation,
Detection of temperature sensor disconnection,
Maintenance reminder, Forced cooling operation for inspection |
Noise (Characteristic A) |
64dB |
Protective category |
Internal circuit : equivalent to IP54 |
Safety/Environmental standard |
PSE/RoHS |
CE,PSE/RoHS |
Body color |
Beige(5Y7/1 corresponding) |
Dimensions(in mm) |
W300×H550×D200 |
Weight |
18.0kg |
Rated frequency (50/60Hz)
- Nominal value when temperatures both inside and outside the control panel are 35℃
- Values at 35℃ temperature both inside and outside are indicated in “Rated” and values at 50℃
outside and 35℃ inside are indicated in “Max.”.
- Use only within the specified temperature range.
●Please contact us for other supply voltages than 200VAC.
Performance diagram

Dimensions (in mm)

Mounting cutout

Mounting view

|