Enclosure cooling unit “COOL CABI”
OCA-300BC-100V
Lateral mounting type (Standard)
Features
- Temperature indication
- High temperature alarm output
- Ease of maintenance
- Mountable either on the outer wall or being recessed as the space demands
- For other details, please go to “Product outline”.
Specifications
Model |
OCA-300BC-100V |
Type of mounting |
Lateral mounting |
Cooling capacity ※1 |
250/300W |
Rated voltage |
Single phase 100VAC±10% |
Current consumption ※2 |
Rated |
2.9/2.7A or less |
Max. |
3.5/3.2A |
Starting current |
7.5/7.2A |
Power consumption ※2 |
Rated |
265/260W |
Max. |
330/320W |
Refrigerant |
R134a (140g) |
Working temperature ※3 |
+20 to+50℃ |
Temperature setting range ※3 |
+30 to +45℃ (Initial setting: +35℃) |
External output |
Alarm output (no voltage c contact: 250VAC/30VDC 3A resistance load) |
Display |
Internal temperature, Alarm code/Operation lamp, Alarm lamp |
Function |
Off-temperature alarm, Detection of abnormal heat dissipation,
Detection of temperature sensor disconnection,
Maintenance reminder, Forced cooling operation for inspection |
Noise (Characteristic A) |
64dB |
Protective category |
Internal circuit : equivalent to IP54 |
Safety/Environmental standard |
PSE/RoHS |
Body color |
Beige(5Y7/1 corresponding) |
Dimensions (in mm) |
W300×H500×D150 |
Weight |
16.0kg |
Rated frequency (50/60Hz)
- Nominal value when temperatures both inside and outside the control panel are 35℃
- Values at 35℃ temperature both inside and outside are indicated in “Rated” and values at 50℃
outside and 35℃ inside are indicated in “Max.”.
- Use only within the specified temperature range.
●Please contact us for other supply voltages than 100VAC.
Performance diagram

Dimensions (in mm)

Mounting cutout

Mounting view