Enclosure cooling unit “COOL CABI”
OCA-2300BCD-200V
Lateral mounting type - Condensate-free
Features
- No electric power required to evaporate condensate water!!
- Innovative three-step evaporation method by means of a pan (1st) and
a fin (2nd) and a supplimentary filter (3rd)
- Achieved high efficiency with less energy making use of cool condensate water to cool down the radiation fin
- Temperature indication
- High temperature alarm output
- Ease of maintenance
- For other details, please go to “Product outline”.
Specifications
Model |
OCA-2300BCD-200V |
Type of mounting |
Lateral mounting |
Cooling capacity ※1 |
2100/2300W |
Rated voltage |
Three phase 200VAC±10% |
Current consumption |
Rated ※2 |
3.4/3.7A or less |
During condensate evaporation ※3 |
3.4/3.7A or less |
Max. ※2 |
4.0/4.8A |
Starting current |
16.0/14.0A |
Power consumption |
Rated ※2 |
975/1130W |
During condensate evaporation ※3 |
960/1130W |
Max. ※2 |
1195/1520W |
COP ※4 |
2.04 |
Refrigerant |
R407C (640g) |
Working temperature ※5 |
+20 to +50℃ |
Working humidity |
85%RH or less, Free from condensation |
Temperature setting range ※5 |
+30 to +45℃ (Initial setting: +35℃) |
External output |
Alarm output (no voltage c contact: 250VAC/30VDC 3A resistance load) |
Temperature and humidity conditions for evaporation |
+35℃ 85%RH or less |
Display |
Internal temperature, Alarm code/Operation lamp, Alarm lamp |
Function |
Off-temperature alarm, Detection of abnormal heat dissipation,
Detection of temperature sensor disconnection,
Maintenance reminder, Forced cooling operation for inspection |
Noise (Characteristic A) |
68dB |
Protective category |
Internal circuit : equivalent to IP54 |
Safety/Environmental standard |
PSE/RoHS |
Body color |
Beige(5Y7/1 corresponding) |
Dimensions(in mm) |
W450×H1150×D250 |
Weight |
52.0kg |
Rated frequency (50/60Hz)
- Nominal value when temperatures both inside and outside the control panel are 35℃
- Nominal values under the following conditions.
Rated : +35℃, 40%RH for outside and +35℃ for inside (free from condensation)
Max : +50℃, 40%RH for outside and +35℃ for inside (free from condensation)
- Nominal value when maximum amount of condensate water is generated under +35℃, 85%RH temperature and humidity conditions for both inside and outside the control panel.
- COP (coefficient of performance) is the ratio of the cooling output to power consumption.
- Use only within the specified temperature range.
Performance diagram

Dimensions (in mm)

Mounting cutout

Mounting view

|