Enclosure cooling unit “COOL CABI”
OCA-1700AC-200V(-CE)
Roof mounting type
Features
- Safety design
- Temperature controller equipped as standard
- Ease of maintenance
- For other details, please go to “Product outline”.
Specifications
Model |
OCA-1700AC-200V |
OCA-1700AC-200V-CE |
Type of mounting |
Roof mounting |
Cooling capacity ※1 |
1550/1700W |
Rated voltage |
Three phase 200VAC±10% |
Current consumption ※2 |
Rated |
4.2/4.4A or less |
Max. |
5.5/5.7A |
Starting current |
15.2/14.0A |
Power consumption ※2 |
Rated |
800/880W |
Max. |
1050/1130W |
Refrigerant |
R407C (480g) |
Working temperature ※3 |
+20 to +50℃ |
Temperature setting range ※3 |
+30 to +45℃ (Initial setting: +35℃) |
External output |
Alarm output (no voltage c contact: 250VAC/30VDC 3A resistance load) |
Display |
Internal temperature, Alarm code/Operation lamp, Alarm lamp |
Function |
Off-temperature alarm, Detection of abnormal heat dissipation,
Detection of temperature sensor disconnection, Maintenance reminder,
Forced cooling operation for inspection, Detection of drain overflows |
Noise (Characteristic A) |
67dB |
Protective category |
Internal circuit : equivalent to IP54 |
Safety/Environmental standard |
PSE/RoHS |
CE, PSE/RoHS |
Body color |
Beige(5Y7/1 corresponding) |
Dimensions(mm) |
W590×H447×D350 |
Weight |
40.0kg |
Rated frequency (50/60Hz)
- Nominal value when temperatures both inside and outside the control panel are 35℃
- Values at 35℃ temperature both inside and outside are indicated in “Rated” and values at 50℃
outside and 35℃ inside are indicated in “Max.”.
- Use only within the specified temperature range.
●Please contact us for other supply voltages than 200VAC.
Performance diagram

Dimensions (in mm)

Mounting cutout

Mounting view

|